Full Load Current: Three Phase AC Motors by Brandy McNeilin Electrical TablesFebruary 16, 2017 Motor Horsepower Motor Ampere Size Breaker Size Starter Heater Ampere Size Wire Size Conduit 1 230V 460 V 4.2 2.1 15 15 00 00 4.830 2.415 12 12 3/4″ 3/4″ 1-1/2 230V 460V 6.0 3.0 15 15 00 00 6.900 3.450 12 12 3/4″ 3/4″ 2 230V 460V 6.8 3.4 15 15 0 00 7.820 3.910 12 12 3/4″ 3/4″ 3 230V 460V 9.6 4.8 15 15 0 0 11.040 5.520 12 12 3/4″ 3/4″ 5 230V 460V 15.2 7.6 15 15 1 0 17.480 8.740 12 12 3/4″ 3/4″ 7-1/2 230V 460V 22 11 40 30 1 1 25.300 12.650 10 12 3/4″ 3/4″ 10 230V 460V 28 14 50 30 2 1 32.200 16.100 10 12 3/4″ 3/4″ 15 230V 460V 42 21 70 40 2 2 48.300 24.150 6 10 1″ 3/4″ 20 230V 460V 54 27 100 50 3 2 62.100 31.050 6 10 1″ 3/4″ 25 230V 460V 68 34 100 50 3 2 78.200 39.100 4 8 1-1/2″ 1″ 1. Overcurrent device may have to be increased due to starting current and load conditions. See NEC 430-52, Table 430-152. Wire based on 75°C terminations and insulation. 2. Overload heater must be based on motor nameplate and sized per NEC 430-32. 3. Conduit size based on Rigid metal conduit with some spare capacity. For minimum size and other conduit types, see NEC Appendix C, or UGLY’S pages 102-122.